Descriptions:
VA-6000MS changeover is an integrated controller supporting main and backup amp swithing, speaker circuit grounding detection, open circuit and short circuit detection; compatible with three or four wire volume controller wiring, without extra wiring or power supply; combining 8 programmable stem node or wet node trigger inputs and 8 programmable on-line output signal. It works with class D amplifiers, traditional amplifiers to provid a safe, affordable solution to the PA & Voice Alarm system.
Features:
● 2U chassis design, high integrated, modularization.
● Support speaker circuit grounding, open circuit and short circuit detection.
● Support 3/4 wire horn circuit wiring.
● 8 programmable trigger input interfaces.
● 8 programmable trigger output interfaces.
● Support power-saving mode when the amplifier has not input signal enters.
● Support lines redundance wiring.
● Support linkage to fire alarm controller.
Basic Functions
* Main amplifier automatic backup switching power amplifier, real-time detection, indicate by different color LEDs.
* Real time monitoring speaker bus loop, power amplifier status, automatic control switch.
* Allows amplifier enter into power saving mode when no signal input to save energy (start through VA-6000ST, default disabled).
* Allows to configure the priority of network and local audio.
* Support power through, even if the main and standby power supply is cut off at the same time (amplifier power supply normal), the local 8 audio signals are not affected.
* 8 stem node or wet node input port, to trigger the pre-pragrammed language information to the specified zones or open the coresposing external power to the corresponding event warning.
* 8 programmable relay signal output port, ouupt no voltage output short circuit relay control signal to the third party equipment to realize on-line automatic control.
* Provide DC 24V standby power input interface ( connect to 24V DC supplied by VA-6000BC).
Specifications:
Model | VA-6000MS |
AC Power Supply | |
Voltage | ~220-240V 50/60Hz |
Maximum Current | 0.3A (not including the 4 wire strong cut output) |
Specification Of The Fuse | 250V/2A, slow speed type |
DC Power Supply | |
Voltage | 24V DC, ±20% |
Maximum Current | 2A (not including the 4 wire strong cut output) |
Power | 48W |
Performance Index | |
Parallel Signal Input / Output | |
Distortion | <1% (rated output power),1KHz |
Frequency | 80Hz~20KHz |
Sensitivity | 385mV |
Impedance | 10KΩ |
S/N Ratio | >70dB |
Contact Output | |
8 Relay Programmable Output | Short circuit, no voltage |
8 ProgrammableTrigger Input | 8 programmable trigger input |
Level Model | Highest 3.3V |
Short Circuit Mode | No voltage, short circuit |
Cooling Way | Air cooled |
Protection | Delay / temperature / short / overload |
Mechanical Index | |
Size (L x W x D) | 484 x 88 x 447 mm (19 inches wide, 2U) |
Weight | About 7.8 Kg |
Installation | Desktop or 19 inch cabinet |
Color | Black |
Environmental Requirements | |
Environmental Requirements | +5℃ ~ +40℃ |
Storage Temperature | -20℃ ~ +70℃ |
Relative Temperature | <95% (no treatment) |
VA-6000MS Front Panel <<
Connectors
1 19 inch rack location hole and machine foot.
2 Main power indicators:
(1) Off - stop working.
(2) Green - in normal power supply.
(3) Yellow - main power fault.
3 DC24V power indicator:
(1) Off - main power is not configured.
(2) Yellow - standby power supply fault.
(3) Green - standby power supply in normal.
4 Network status indicator:
(1) Yellow - disconnected from the network.
(2) Tgreen - network in normal.
5 The main amplifier 1~8 channel state indicator:
(1) Green - power amplifier work.
(2) Yellow - power amplifier fault.
(3) Red - the main amplifier fault, the duty of the current falut main power amplifier has shifted to the standby power amplifier.
6 6 standby power amplifier work state description:
(1) Green - power amplifier work.
(2) Yellow - power amplifier fault.
(3) Red - the main amplifier fault, the duty of the current falut main power amplifier has shifted to the standby power amplifier.
VA-6000MS Back Panel <<
Connectors
1 8 parallel signal and audio power amplifier sleep signal output interfaces ,connecting to external amplifier signal input .
2 8 local parallel audio signal input interfaces, connecting to external parallel audio signal output device.
3 1~8 partition audio power signal output, connecting to external speaker or a three / four wire voice control box.
4 Standby power amplifier audio signal output.
5 Backup audio power signal input.
6 CAN bus interface, connecting to external VA-6000BC.
7 8 programmable trigger signal input ( level signal or short-circuit no voltage signal input).
8 8 programmable relay output signal.
9 Network interface.
10 Backup power supply input interface connecting to external VA-6000BC DC power supply output.
11 Chassis ground (Note: please ensure the reliable grounding).